ELECTRO MAGNETIC RELEASES RIXSON

Electromagnetic Door Releases

Electromagnets designed specifcally to hold fire and smoke barrier doors open until released by remote smoke detector or other switching device. Cap assembly consists of armalture contact plate w/ adjustable pivot mounting for installation on the door, and heavy-duty electromagnet mounted on the wall or floor behind the door. Door must have a separate door closer to work in conjunction with these magnets. In order to meet life safety codes must be tied into a fire alarm system.

  • Approximately 35 lbs holding force.
  • Fail safe operation. Power failure releases door to close, positive release button initiates closing motion.
  • UL and ULC listed.
  • California state fire marshall listing #3550-047.
  • Finishes: (SA) Sprayed aluminum or (SB) sprayed bronze.

Model Number 990
Typical Usage Low Profile; Concealed Wiring
Total Projection 1 7/8"
Mounting Requirement 2" x 4" x 2 1/2" Outlet Box
Model Number 996
Typical Usage Surface Wiring
Total Projection 4"
Mounting Requirement 1 1/2" Deep Adapter Housing
Model Number 997
Typical Usage Recessed Doors; concealed Wiring
Total Projection 2 1/2"
Mounting Requirement 2" x 4" x 1 3/4" Outlet Box
Model Number 998
Typical Usage Standard Doors; Concealed Wiring
Total Projection 3 1/2"
Mounting Requirement 2" x 4" x 1 3/4" Outlet Box
Model Number 999
Typical Usage Universal Mounting Base Plate; Concealed Wiring
Total Projection 4 3/8"
Mounting Requirement 2" x 4" Outlet Box; 4" Square Box; 4" Octagonal Box
Model Number 980
Typical Usage Floor Mount; Single Door; Concealed Wiring
Total Projection 6 5/8"
Mounting Requirement Conduuit connects directly to floor plate
Model Number 981
Typical Usage Floor Mount; 2 Back-to-Back Doors; Concealed Wiring
Total Projection 8 1/4"
Mounting Requirement Conduit connects directly to floor plate

 

Voltage and Current All Models except 981 Model 981 (only)
120VAC 60 hz .017 amp .034 amp
24VAC 60 hz .080 amp .160 amp
24VDC - .068 amp .136 amp
12VDC - .180 amp .360 amp
250VAC 50/60 hz .009 amp .018 amp

 

Replacement Mags
996210 Magnet Asy.-120V AC (980, 981, 990, 990 Only)
996211 Magnet Asy.-24V AC/DC (980, 981, 990, 999)
996212 Magnet Asy.-24V DC (980, 981, 990, 990 Only)
996213 Magnet Asy.-12V DC (980, 981, 990, 990 Only)
998361 Magnet Asy.-120V AC (997, 998)
998362 Magnet Asy.-24V AC/DC (997, 998)
998363 Magnet Asy.-24V DC (997, 998)
998364 Magnet Asy.-12V dC (997, 998)
996361 Magnet Asy.-120V AC (996)
996362 Magnet Asy.-24V AC/DC (996)
996363 Magnet Asy.-24V DC (996)
996364 Magnet Asy.-12V AC (996)

 